SINCE 1 9 1 1

Product groups



deutsche Version
THREE-PHASE MAINS MONITOR
DNW-400

Type

DNW 100, DNW 400, DNW 500, DNW 690

Input


 

Rated voltages 100V, 400V, 500V, 690V
Without and with neutral conductor monitoring
(can be selected via connection).

Monitoring







 

Phase sequence (rotating field)
Neutral conductor break
Phase failure
Overvoltage, can be set between
5 and 20%
Undervoltage, can be set between
5 and 20%
Unbalance, can be set between
5 and 15%

Output

 

2 floating changeover contacts
Relay release time, can be set between 0.3 and 7.5 s.

LED display



 

Overvoltage and undervoltage
Unbalance
Neutral conductor break
Phase sequence
Relay function

Design
 

Compact design, 22.5 mm wide
Fixed on DIN rail

 

 

The DNW... type three-phase mains monitor is used for the comprehensive monitoring of a three-wire or four-wire mains for phase failure, neutral conductor break, overshooting or undershooting of the three phase voltages, unbalance of the three phase voltages and the phase sequence (rotating field). An auxiliary supply is not required.

Data sheet (pdf-document)